In a direct-expansion (DX) unitary system, the evaporator is in direct contact with the air stream, so the cooling coil of the airside loop is also the evaporator of the refrigeration loop. The term “direct” refers to the position of the evaporator with respect to the airside loop.

The term "expansion" refers to the method used to introduce the refrigerant into the cooling coil. The liquid refrigerant passes through an expansion device (usually a valve) just before entering the cooling coil (the evaporator). This expansion device reduces the pressure and temperature of the refrigerant to the point where it is colder than the air passing through the coil.

The components of the DX unitary system refrigeration loop (evaporator, compressor, condenser, expansion device and even some unit controls) may be packaged together, which provides for factory assembly and testing of all components, including the electrical wiring, the refrigerant piping, and the controls. This is called a Packaged DX system.

Alternatively, the components of the refrigeration loop may be split apart, allowing for increased flexibility in the system design. This is called a Split DX system. Separating the elements has the advantage of providing the system design engineer with complete flexibility to match components in order to achieve the desired performance.

One of the most common reasons for selecting a DX system, especially a packaged DX system, is that, in a smaller building, it frequently has a lower installed cost than a chilled-water system because it requires less field labor and has fewer materials to install. Packaged DX systems that use air-cooled condensers can be located on the roof of a building, in a small equipment room, or even within the perimeter wall of the building.

Additionally, if the tenants are paying the utility bills, multiple packaged DX units may make it easier to track energy use, as only the specific unit serving that tenant would be used to meet the individual cooling or heating requirements.

Factors affecting the decision to select DX Unitary or Chiller-Based Applied systems include:

  • Installed Cost
  • Energy consumption
  • Space requirements
  • Freeze prevention
  • Precision
  • Building height, size, shape
  • System cooling and heating capacity
  • Centralized maintenance
  • Stability of control
  • Individual tenant billing

One of the services Trane offers is a comprehensive design and energy analysis to help you consider all factors in selecting the correct type of system for your project.

  Locate a Trane Sales Office
Products

Products

Get detailed information on all Trane HVAC products.

    Controls Training

    Controls Training

    Learn fundamentals or how to troubleshoot specific systems.
    More Information on Controls and Automation Training

      Building Services

      Building Services

      See how we can help make your building work better for life.

        Energy, IAQ and the Environment

        Energy, IAQ and the Environment

        See how Trane can help you create and sustain High Performance Buildings for Life™.

          Systems Integration

          Systems Integration

          When you need open systems solutions, Trane can solve your interoperability and performance optimization issues.

          Performance Agreement for Comfort (PACT™)

          Performance Agreement for Comfort (PACT™)

          See how performance-based solutions can guarantee savings and help you finance your project.

            Product Literature

            Product Literature

            View or download product catalogs, technical data and manuals.